SDi DB02 Checker Sound Level Meter, Frequency Weighting

& Free Shipping

  • Ideal for maintenance of fire and security alarm systems
  • Easy to use
  • Unit conforms to the IEC651 type 2, ANSI S1.4 Type 2 (Required by NFPA 72 Chapter 14, 14.4.2.2.(15))
  • Designed to meet the requirements of Life Safety Engineers

Special Order

SKU: 2S-DB02 Category: Brand:

Description

dbcheckerโ„ข is ideal for testing audible appliances for the public operating mode of an emergency voice/alarm system in accordance with manufacturers instructions.

  • Ideal for maintenance of fire and security alarm systems
  • Easy to use
  • Unit conforms to the IEC651 type 2, ANSI S1.4 Type 2 (Required by NFPA 72 Chapter 14, 14.4.2.2.(15))
  • Designed to meet the requirements of Life Safety Engineers
  • Display with 01.dB steps on a 4-digit LCD
  • Range from 40 to 130 dB over four ranges
  • Frequency weighting: A

WHY dBchecker?

Merely “listening” or utilizing any sound level meter available is not a reliable method for testing audible alarm notification appliances. Many of the meters currently on the market do not meet the requirements for NFPA 72. dBcheckerโ„ข conforms to ANSI S1.4a, which is required to meet the standard set forth in the latest edition of the National Fire Alarm Code. (NFPA72)

HIGHEST STANDARDS

” ….only sound level meters that comply with ANSI S1.42 should be used for the assessment of fore alarm systems…”

” …Testing of Audible Alarm Notification Appliances shall be done upon initial acceptance and semi-annually”

” …Sound pressure shall be measured with sound level meter meeting ANSI S1.4a, Specifications for Sound Level Meters, Type 2 Requirements. Levels throughout the protected area shall be measured and recorded….” NFPA72 14.4.2.2 (15)

Additional information

Weight 1 lbs
Brand