- Base Diameter: 6.2 inches (157 mm)
- Base Height: 0.95 inches (24 mm)
- Weight: 0.3 lb. (137 g)
Want to be notified when this product is back in stock?
Description
The Model B112LP detector base is designed for use with System Sensor models 2151 photo electronic and 1151 ionization detector heads. This two-wire base is equipped with screw terminals for the connection of power, ground, and an optional remote annunciator.
Main Features
- Base Diameter: 6.2 inches (157 mm)
- Base Height: 0.95 inches (24 mm)
- Weight: 0.3 lb. (137 g)
- Mounting: 4-inch square box with or without plaster ring. Min. depthโ1.5 inches / 3-1/2-inch octagon box. Min. depthโ1.5 inches
- Operating Temperature Range: 0ยฐ to 49ยฐC (32ยฐ to 120ยฐF)
- Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
- Electrical Ratings – includes base and detector
- System Voltage: 24 VDC
- Maximum Ripple Voltage: 4 Volts peak-to-peak
- Start-Up Capacitance: 0.02ยตF Maximum
- Standby Ratings: 20 VDC Minimum / 29 VDC Maximum / 120 ยตA Maximum
- Alarm Ratings: 17 mA Minimum / 36 mA Maximum
- Reset Voltage: 1.4 VDC Minimum
- Reset Time: 0.3 Seconds Maximum
- (The optional RA400Z operates within specified detector alarm currents.)
- Start-up Time: 34.0 Seconds Maximum
- Relay Contact Ratings:
- Resistive or Inductive (60% Power Factor)
- Form A: 2.0 A @ 30 VAC/DC
- Form C: 2.0 A @ 30 VAC/DC / 0.6 A @ 110 VDC / 1.0 A @ 125 VAC